Catálogo
Warning!  You must be logged in to download documents. If not, you will be redirected to the login page

SÉRIE ISOLATORS-EX[GD]

INTERRUPTOR/SECCIONADOR

32A 3/4P IP66 150x220x120mm II 2GD GENERAL GREY/BLACK

Cod. 591.SGE3204

The ISOLATORS-EX[GD] Series SWITCH DISCONNECTOR is engineered for robust performance in demanding environments. Designed for GENERAL applications, it supports a rated current of 32A and is available in 3/4P configurations. The device boasts a high protection degree of IP66, ensuring resilience against dust and water ingress. Certified under Group and Categories EX: II 2GD, it is suitable for use in potentially explosive atmospheres, adhering to ATEX standards. The surface mounting version is constructed from durable STAINLESS STEEL [AISI316L], finished in a GREY/BLACK color scheme. The enclosed construction type offers enhanced safety, with an impact resistance of 7J. The handle is padlockable in both OFF (accommodating 3 padlocks) and ON (1 padlock) positions, providing secure operation. An earth-stud is included for additional safety measures. This product is meticulously designed to meet the rigorous demands of industrial electrical installations.
Série ISOLATORS-EX[GD]
INTERRUPTOR/SECCIONADOR
Na caixa
PAREDE
AÇO INOX [AISI316L]
IP66
GENERAL
CINZA/PRETO
32A
3/4P
150x220x120mm
2xM32
ø16-25mm
7J
ø6mm
II 2GD
-35 °C
55 °C
690VAC
32A
32A
25A
10mm²
16mm²
0,8Nm
  • Alça bloqueado na posiçao OFF (3 cadeados) e na posiçao ON (1 cadeado).
  • AtEX [ATmosphères EXplosibles]: para aplicações em atmosferas potencialmente explosivas.
  • Pino de ligação à terra incluído

Product

EAN code
8001636296821
INTRASTAT code
8536508000
Net weight
2.849 KG
Quantidade Mínima
1

Packaging

Packaging Box
Quantity
1
EAN code
8001636296821
Depth
275.0 MM
Width
220.0 MM
Height
160.0 MM
Volume
9680.0 CCM
EN 60947-1/A1 (2011) [European Standard] Low-voltage switchgear and controlgear - Part 1: General rules
EN IEC 60079-0 (2018) [European Standard] Explosive atmospheres - Part 0: Equipment - General requirements
EN 60947-1/A2 (2014) [European Standard] Low-voltage switchgear and controlgear - Part 1: General rules
DIRECTIVE ATEX 2014/34/UE [European Directives] Atmosphere Explosive
IEC 60079-0 (2017) [International Standard] Explosive atmospheres - Part 0: Equipment - General requirements
EN 60079-7 (2018) [European Standard] Explosive atmospheres. - Part 7: Equipment protection by increased safety "e"
IEC 60079-1 (2014) [International Standard] Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d".
EN 60079-1 (2014) [European Standard] Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosures 'd'
IEC 60079-31 (2013) [International Standard] Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
EN 60947-3/A2 (2015) [European Standard] Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
EN 60947-3/A1 (2012) [European Standard] Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
IEC 60079-7 (2017) [International Standard] Explosive atmospheres - Part 7: Equipment protection by increased safety "e".
EN 60947-1 (2007) [European Standard] Low-voltage switchgear and controlgear - Part 1: General rules
EN 60079-31 (2014) [European Standard] Explosive atmospheres. Equipment dust ignition protection by enclosure "t"
EN 60079-7 (2015) [European Standard] Explosive atmospheres. Equipment protection by increased safety "e"
EN 60947-3 (2009) [European Standard] Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
thumbnail
Notifica ATEX
Product quality assurance notification
thumbnail
SGS ECAS Atex
Société Générale de Surveillance SA, Switzerland
thumbnail
Notifica ATEX
Product quality assurance notification
thumbnail
INERIS Atex
Institut National de l'Environnement Industriel et des Risques
thumbnail
CPEx INMETRO Atex
Centro de Pesquisas em Atmosfera Explosiva
thumbnail
UKCA marking [ELEMENT UKCA ATEX]
UK Conformity Assessed
thumbnail
INERIS IECEx
Institut National de l'Environnement Industriel et des Risques
thumbnail
UKCA marking
UK Conformity Assessed
thumbnail
UE
Declaratiòn de conformidad
Você precisa da Folha Técnica do produto ?
Você precisa de Documentação ou Certificação do produto ?

Tem o número de série do seu produto ?