Catálogo
Warning!  You must be logged in to download documents. If not, you will be redirected to the login page

SÉRIE ISOLATORS-EX[GD]

INTERRUPTOR/SECCIONADOR

20A 2P IP66 160x160x90mm II 2GD GENERAL GREY/BLACK GW 960°C

Cod. 591.PGE2002-A

The ISOLATORS-EX[GD] Series offers a robust SWITCH DISCONNECTOR designed for industrial applications requiring high safety standards. This GENERAL type switch disconnector is rated for a current of 20A and features a 2P configuration. It boasts an IP66 protection degree, ensuring reliable performance in harsh environments. The device is classified under Group and Categories EX: II 2GD, making it suitable for use in potentially explosive atmospheres, as indicated by its ATEX certification. The surface mounting version is constructed from durable engineering plastic in a grey/black color scheme. The enclosed construction type provides an impact resistance of 7J, enhancing its durability. The handle is padlockable in both the OFF (accommodating 3 padlocks) and ON (1 padlock) positions, offering additional security. This product is engineered to meet the rigorous demands of industrial settings, ensuring safety and reliability.
Série ISOLATORS-EX[GD]
INTERRUPTOR/SECCIONADOR
Na caixa
PAREDE
TECNOPOLÍMERO
IP66
GENERAL
CINZA/PRETO
20A
2P
160x160x90mm
2xM25
ø8-18mm
Low temperature [-50°C]
GW 960°C
7J
ø6mm
II 2GD
-50 °C
60 °C
690VAC
20A
20A
20A
10mm²
16mm²
0,8Nm
  • Alça bloqueado na posiçao OFF (3 cadeados) e na posiçao ON (1 cadeado).
  • AtEX [ATmosphères EXplosibles]: para aplicações em atmosferas potencialmente explosivas.

Product

EAN code
8001636347547
INTRASTAT code
8536508000
Net weight
1.987 KG
Quantidade Mínima
1

Packaging

Packaging Box
Quantity
1
EAN code
8001636347547
Depth
275.0 MM
Width
220.0 MM
Height
160.0 MM
Volume
9680.0 CCM
EN 60947-1/A1 (2011) [European Standard] Low-voltage switchgear and controlgear - Part 1: General rules
EN IEC 60079-0 (2018) [European Standard] Explosive atmospheres - Part 0: Equipment - General requirements
DIRECTIVE ATEX 2014/34/UE [European Directives] Atmosphere Explosive
IEC 60079-1 (2014) [International Standard] Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d".
EN 60947-1/A2 (2014) [European Standard] Low-voltage switchgear and controlgear - Part 1: General rules
IEC 60079-0 (2017) [International Standard] Explosive atmospheres - Part 0: Equipment - General requirements
EN 60079-7 (2018) [European Standard] Explosive atmospheres. - Part 7: Equipment protection by increased safety "e"
IEC 60079-31 (2013) [International Standard] Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
EN 60079-1 (2014) [European Standard] Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosures 'd'
EN 60947-3/A2 (2015) [European Standard] Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
EN 60947-3/A1 (2012) [European Standard] Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
IEC 60079-7 (2017) [International Standard] Explosive atmospheres - Part 7: Equipment protection by increased safety "e".
EN 60947-1 (2007) [European Standard] Low-voltage switchgear and controlgear - Part 1: General rules
EN 60079-31 (2014) [European Standard] Explosive atmospheres. Equipment dust ignition protection by enclosure "t"
EN 60079-7 (2015) [European Standard] Explosive atmospheres. Equipment protection by increased safety "e"
EN 60947-3 (2009) [European Standard] Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
thumbnail
Notifica ATEX
Product quality assurance notification
thumbnail
UKCA ATEX Notification
UK Quality Assurance Notification
thumbnail
SGS ECAS Atex
Société Générale de Surveillance SA, Switzerland
thumbnail
Notifica ATEX
Product quality assurance notification
thumbnail
INERIS Atex
Institut National de l'Environnement Industriel et des Risques
thumbnail
CPEx INMETRO Atex
Centro de Pesquisas em Atmosfera Explosiva
thumbnail
UKCA marking [ELEMENT UKCA ATEX]
UK Conformity Assessed
thumbnail
INERIS IECEx
Institut National de l'Environnement Industriel et des Risques
thumbnail
UKCA marking
UK Conformity Assessed
thumbnail
UE
Declaratiòn de conformidad
Você precisa da Folha Técnica do produto ?
Você precisa de Documentação ou Certificação do produto ?

Tem o número de série do seu produto ?

Aprofundamento

Produtos relacionados

Scame Parre S.p.a
Via Costa Erta 15
24020 Parre (BG) -  Italy
Via Costa Erta 15
24020 Parre (BG) -  Italy
Via Costa Erta 15
24020 Parre (BG) -  Italy

A paragraph is a self-contained unit of a discourse in writing dealing with a particular point or idea. Paragraphs are usually an expected part of formal writing, used to organize longer prose.