SERIES DETAILS
INNOVA Series
Control devices - Double pole switches

REFERENCE STANDARDS
|
BS EN 60669-1
Switches for household and similar fixed-electical installations. Part 1: General requirements. |
|
TECHNICAL DATA SHEET
|
Rated current |
20A-45A |
|
Rated voltage |
250V~ |
|
Frequency |
50Hz |
|
Insulating voltage |
250V~ |
|
Protection degree |
IP20D |
|
Operating temperature according to the reference standard |
-5°C +40°C |
|
Maximum operating temperature |
60°C |
|
Cabling capacity of the terminal |
20A: 3x2,5mm² - 2x4mm² - 1x6mm² |
|
Cabling capacity of the terminal |
45A: 4x4mm² - 3x6mm² - 1x16mm² |
|
Glow Wire test |
850°C |
|
Material |
Engineering plastic |
|
Mounting box type |
Flush: 1-2 gang (min. depth: 35mm) |
|
Mounting box type |
Surface: 1-2 gang (min. depth: 35mm) |
|
Colour |
White RAL 9016 |
|
Colour |
Ivory RAL 1015 |
|
Operating testing |
40.000 operations at rated current |
|
Operating testing |
100.000 operations for mechanical life |
|
Max installation altitude |
2.000m |
|
BEHAVIOUR WITH CHEMICAL AND ATMOSPHERIC AGENTS
|
Saline solution |
Resistant
|
|
Acids |
Concentrated |
Limited resistance
|
Diluted |
Resistant
|
|
Bases |
Concentrated |
Limited resistance
|
Diluted |
Resistant
|
|
Solvents |
Hexane |
Resistant
|
Benzol |
Not resistant
|
Acetone |
Not resistant
|
Alcohol |
Resistant
|
|
Mineral oil |
Limited resistance
|
|
UV rays |
Resistant
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Discover how to find in thousands configurations, the Combination unit for you. |
|
|
|
|
Identifies the products compatible with Scame material. |
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|